Proje Açıklaması

Current Transformer

  • Frequency : 50 Hz, 60 Hz.
  • Secondary Current : 1 A, 2 A or 5 A. others on request.
  • Primary Current : Up to 4000 A
  • Thermal and Dynamic Ratings : Short time thermal current ratings up to 50 KA / 3 sec and dynamic current ratings up to 125 KA peak.
  • Continuous Thermal Current : 1.2 x In continuous (up to 2.0 x In on request).
  • Standards : IEC, BS, ANSI, AS other standards on request. Insulation

Voltage Transformer

  • Frequency : 50 Hz, 60 Hz.
  • Rated Secondary Voltage : 1 10/V3, 100/V3 V etc. in conformity with customer requirement.
  • Rated Tertiary Voltage : 110/V3, 100/V3, 110/3, 100/3, 100, 110V etc. in conformity with customer requirement.
  • Highest System Voltage : Highest system voltage from 36 to 420 kV.
  • Number of Secondary Windings : In conformity with customer requirements.
  • Voltage factor : 1.2 x Un continuous /1.5 x Un for 30 sec. or 1.9x un for 8 hrs.
  • Standards : IEC, BS, ANSI, AS, other standards on request.
HV Current and Voltage Transformers
HV Current and Voltage Transformers